Power station battery current calculator

Built for portable power stations and their battery packs — 12V, 24V and 48V DC buses, LiFePO4 cells, inverter-fed AC loads. Tell the calculator what you already know: watts and volts, volts and ohms, or capacity and runtime, and it returns the amps the pack is actually delivering, with the working shown.

Scope: this is a sizing tool for power station hardware, not a general electronics or physics reference. The assumptions are a DC battery bus, a LiFePO4 pack and an 85–90% inverter path. It does not model AC impedance, power factor, three-phase circuits, motor inrush curves or lead-acid Peukert behaviour — for those, use a textbook or a dedicated AC tool.

Load & battery voltage
Formula
I = P ÷ (V × η)

P is the load in watts, V the DC bus voltage, η the inverter and wiring efficiency. This is the formula behind cable, fuse and BMS sizing.

Current draw24.5 A
Fuse size ×1.25 margin30.6 A
Your numbers1,000W ÷ (48V × 85%)

= 24.5 A from the battery. The same wattage on 12V would pull 98.0 A — which is why low-voltage systems need such heavy cable.

The current above is on the battery side. An AC appliance rated 1,000W draws only ~8.3A at 120V — same power, different side of the inverter.

Three routes, one answer

Which formula matches what you know

Every tab above answers the same question from different inputs. Pick the one that matches the number printed on your device, your battery or your invoice — and read the note under each card for what the result is good for.

You know the watts and the battery voltage

Every appliance label hands you watts, and a station spec sheet hands you volts. Divide one by the other and you have the current the battery must supply. A 1,000W load on a 48V bus is 24.5A; the same load on 12V is 98A. Apply the 85–90% inverter efficiency and both figures climb by roughly a sixth. This is the arithmetic behind cable gauge, fuse rating and BMS choice.

You know the voltage and the resistance

Resistance is the second road to the same answer, and the one that explains failures. Across a small resistor it sizes a load; across a battery's internal resistance it estimates the short-circuit current. A 12V LFP pack at 5 mΩ delivers 2,400A into a dead short, which is why the main fuse sits within inches of the positive terminal on any DIY build — see the component guide.

You only know the capacity in mAh

mAh measures charge, not current, so it cannot be converted without a discharge time — the first point Anker SOLIX's guide to calculating amps from mAh makes. Divide by 1,000 for Ah, divide again by the hours the pack lasts, then take the 80–90% derate it recommends for small electronics. A 10,000mAh pack over 5 hours reads 2A at face value and about 1.8A once derated — not the 10A the label suggests.


How it works

Why the three answers don't agree

They are not competing formulas — they describe the same current from three different pairs of known values. Where people go wrong is at the seams: mistaking AC amps for DC amps, skipping the efficiency derate, or treating mAh as if it were a current rating.

From power

I = P ÷ (V × η)

P in watts, V the DC bus, η the inverter and wiring efficiency as a decimal.

From resistance

I = V ÷ R

R in ohms. With a pack's internal resistance this returns the short-circuit current.

From capacity

I = (mAh ÷ 1000 × η) ÷ h

Convert to Ah first, derate, then divide by the discharge hours.

Five places the maths goes wrong

  • Watts sit on both sides of the inverter

    A 1,000W appliance draws ~8.3A at 120V AC but ~24.5A at 48V DC on the battery side. Same power, different current — mix the two up and the cable you buy is a quarter the size it should be.

  • mAh only compares at the same voltage

    10,000mAh at 3.7V holds 37Wh; at 12V the same label holds 120Wh. Multiply Ah × V before comparing a power bank with a station module.

  • Capacity never sets output current

    A station packed with 20,000mAh of cells still caps at 10A on its 12V car socket, because the port and BMS say so. Capacity decides duration, hardware decides rate.

  • Voltage sag raises the current

    As a pack drains, its terminal voltage falls, so a fixed-wattage load pulls more amps — heating cables and tripping inverters near the bottom of their range.

  • Rated capacity is not usable capacity

    Plan with 85% and derate again for cold and age. Rated Ah measured on a bench in a lab is not what a -5°C morning will hand you.

The mAh route follows Anker SOLIX's published method — capacity ÷ 1,000 for Ah, ÷ hours for amps, then an 80–90% real-world derate. Their point that mAh cannot be compared across voltages is the reason this site plans in watt-hours everywhere else.


Questions & answers

Battery current FAQ

Can I convert mAh to amps without knowing the time?

No. mAh is a quantity of charge; amps is the rate it leaves the pack. The same 10,000mAh station pack can deliver 10A for one hour or 1A for ten — the capacity is identical, the current is not. Anker SOLIX makes this the first caveat in their mAh-to-amps walkthrough, and it is the mistake behind most inflated runtime claims on station and power bank listings.

Which formula do I use for fuse and cable sizing?

The wattage one, because that is what the load actually tells you: I = P ÷ (V × η). Then size the fuse at 1.25× that current and keep the fuse rating below the cable's ampacity — a fuse protects the wire, not the appliance. On a 48V build a 2,000W inverter pulls about 49A, so a 60A fuse on 4 AWG covers it with margin.

Why does a 2,000W inverter draw nearly 200A on 12V?

2,000 ÷ 12 = 167A at face value, and 196A once the 85% efficiency is included. That is not a rounding problem, it is the reason 12V systems cap out around 2–3kW: 200A needs 2/0 cable, a 250A fuse and a BMS rated far above the inverter. High current also means more heat and more fan noise — the noise distance calculator puts a number on that trade-off. The G Series sidesteps it with a 48V bus, where the same 2,000W pulls about 49A and 4 AWG is plenty.

Does a bigger mAh rating mean more output current?

No. Output current is set by the port and the BMS, not by capacity. A station packed with 20,000mAh of cells still stops at 10A on its 12V car socket, because that is what the port is rated for. Capacity decides how long, the port decides how fast — and that difference is why mAh-heavy listings still fail to start a fridge or a circular saw.

Why does the calculator default to 85% efficiency?

Because that is the same factor behind every runtime estimate on this site, and it sits inside the 80–90% range Anker cites for small electronics. Inverter heat, cable resistance, connector losses and voltage conversion all land in that gap. If you are modelling a DC load with no inverter in the path, raise it to 97–99% — the losses are then just wiring.

Which voltage do I enter for a portable power station?

The DC bus voltage, not the AC outlet. A G Series station runs a 48V LFP architecture, so a 3,300W AC load is roughly 3,300 ÷ (48 × 0.85) ≈ 81A from the cells — while only 27.5A flows on the 120V AC side. The same 48V architecture runs through the 2,400Wh expansion battery, and the P Series publishes it on the P2400 spec line (2,160Wh · 45Ah · 48V); for the P600 and P1200, check the voltage printed on the station before trusting a preset. If you are sizing an energy budget rather than a cable, use the power station size calculator instead; it works in watt-hours.

Is this a general electronics calculator?

No — it is scoped to power station hardware. Every number assumes a DC battery bus, a LiFePO4 pack and an inverter at 85–90% efficiency, because those are the products this site sells. If you are studying circuit theory, sizing an AC distribution board, or working with three-phase or motor loads, a physics text or an AC-specific tool will give you the right model; the arithmetic here is deliberately simplified to the questions a station buyer actually asks.